mm2线规对照表补充载流量列(PVC明敷/XLPE空气中参考值)及降额要点

This commit is contained in:
2026-08-28 16:17:35 +08:00
parent 6bae8a82af
commit c66a44d142
2 changed files with 59 additions and 50 deletions
+23 -23
View File
@@ -1,23 +1,23 @@
标称截面mm2,等效实心直径mm,Class1/2铜电阻_20C_Ohm_per_km,Class5软铜电阻_20C_Ohm_per_km,约等AWG,常见用途
0.5,0.798,36.0,39.0,20,信号线、弱电控制线、屏蔽引线
0.75,0.977,24.5,26.0,18,控制线、灯线、二次回路
1.0,1.128,18.1,19.5,17,控制回路、仪器仪表引线
1.5,1.382,12.1,13.3,15,环路线圈本体、照明支路
2.5,1.784,7.41,7.98,13,环路线圈本体、插座回路、道闸电源
4,2.257,4.61,4.95,11,道闸/电机主回路、空调回路
6,2.764,3.08,3.3,9,道闸电机、小功率设备进线
10,3.568,1.83,1.91,7,设备电源进线、充电桩支路
16,4.514,1.15,1.21,5,配电支路、充电桩回路
25,5.642,0.727,0.78,3,配电干路、进线
35,6.676,0.524,0.554,2,总进线、充电桩干线
50,7.979,0.387,0.386,1/0,总进线、母排连接
70,9.441,0.268,0.272,2/0,大功率进线
95,10.998,0.193,0.206,3/0,低压出线、大功率回路
120,12.361,0.153,0.161,4/0,低压主进线
150,13.820,0.124,0.129,,低压主进线
185,15.348,0.0991,0.106,,低压主进线
240,17.481,0.0754,0.0801,,低压主进线、密集型母线
300,19.544,0.0601,0.0641,,低压主进线、母线槽
400,22.568,0.047,0.0486,,大截面电缆、母线
500,25.231,0.0366,0.0384,,大截面电缆、母线
630,28.322,0.0287,0.0287,,大截面电缆、母线
标称截面mm2,等效实心直径mm,Class1/2铜电阻_20C_Ohm_per_km,Class5软铜电阻_20C_Ohm_per_km,约等AWG,常见用途,PVC载流量参考A,XLPE载流量参考A
0.5,0.798,36.0,39.0,20,信号线、弱电控制线、屏蔽引线,10,
0.75,0.977,24.5,26.0,18,控制线、灯线、二次回路,13,
1.0,1.128,18.1,19.5,17,控制回路、仪器仪表引线,16,
1.5,1.382,12.1,13.3,15,环路线圈本体、照明支路,20,24
2.5,1.784,7.41,7.98,13,环路线圈本体、插座回路、道闸电源,27,32
4,2.257,4.61,4.95,11,道闸/电机主回路、空调回路,36,42
6,2.764,3.08,3.3,9,道闸电机、小功率设备进线,46,54
10,3.568,1.83,1.91,7,设备电源进线、充电桩支路,63,57
16,4.514,1.15,1.21,5,配电支路、充电桩回路,85,76
25,5.642,0.727,0.78,3,配电干路、进线,112,101
35,6.676,0.524,0.554,2,总进线、充电桩干线,138,124
50,7.979,0.387,0.386,1/0,总进线、母排连接,168,149
70,9.441,0.268,0.272,2/0,大功率进线,213,188
95,10.998,0.193,0.206,3/0,低压出线、大功率回路,258,226
120,12.361,0.153,0.161,4/0,低压主进线,299,261
150,13.820,0.124,0.129,,低压主进线,344,299
185,15.348,0.0991,0.106,,低压主进线,392,340
240,17.481,0.0754,0.0801,,低压主进线、密集型母线,461,400
300,19.544,0.0601,0.0641,,低压主进线、母线槽,530,458
400,22.568,0.047,0.0486,,大截面电缆、母线,620,540
500,25.231,0.0366,0.0384,,大截面电缆、母线,705,620
630,28.322,0.0287,0.0287,,大截面电缆、母线,800,720
1 标称截面mm2 等效实心直径mm Class1/2铜电阻_20C_Ohm_per_km Class5软铜电阻_20C_Ohm_per_km 约等AWG 常见用途 PVC载流量参考A XLPE载流量参考A
2 0.5 0.798 36.0 39.0 20 信号线、弱电控制线、屏蔽引线 10
3 0.75 0.977 24.5 26.0 18 控制线、灯线、二次回路 13
4 1.0 1.128 18.1 19.5 17 控制回路、仪器仪表引线 16
5 1.5 1.382 12.1 13.3 15 环路线圈本体、照明支路 20 24
6 2.5 1.784 7.41 7.98 13 环路线圈本体、插座回路、道闸电源 27 32
7 4 2.257 4.61 4.95 11 道闸/电机主回路、空调回路 36 42
8 6 2.764 3.08 3.3 9 道闸电机、小功率设备进线 46 54
9 10 3.568 1.83 1.91 7 设备电源进线、充电桩支路 63 57
10 16 4.514 1.15 1.21 5 配电支路、充电桩回路 85 76
11 25 5.642 0.727 0.78 3 配电干路、进线 112 101
12 35 6.676 0.524 0.554 2 总进线、充电桩干线 138 124
13 50 7.979 0.387 0.386 1/0 总进线、母排连接 168 149
14 70 9.441 0.268 0.272 2/0 大功率进线 213 188
15 95 10.998 0.193 0.206 3/0 低压出线、大功率回路 258 226
16 120 12.361 0.153 0.161 4/0 低压主进线 299 261
17 150 13.820 0.124 0.129 低压主进线 344 299
18 185 15.348 0.0991 0.106 低压主进线 392 340
19 240 17.481 0.0754 0.0801 低压主进线、密集型母线 461 400
20 300 19.544 0.0601 0.0641 低压主进线、母线槽 530 458
21 400 22.568 0.047 0.0486 大截面电缆、母线 620 540
22 500 25.231 0.0366 0.0384 大截面电缆、母线 705 620
23 630 28.322 0.0287 0.0287 大截面电缆、母线 800 720
+35 -26
View File
@@ -4,32 +4,35 @@
> 直径列为**等效实心圆导体直径** d=2√(A/π);绞合导体实际外径约大 8%~15%,以电缆制造商样本为准。
> 载流量为**工程参考值**(保守口径):PVC 列=铜芯 BV 线空气中明敷、环境 30°C、单根;XLPE 列=铜芯 YJV 电缆空气中敷设、环境 40°C。实际需按敷设方式(穿管/桥架/直埋)、环境温度、并敷根数、绝缘老化等**降额**,正式设计查《工业与民用配电设计手册》或 GB/T 16895 系列。
> AWG 列为**截面最接近**的近似对照(中国工程选型以 mm² 为准)。
| 标称截面 (mm²) | 等效直径 (mm) | Class 1/2 电阻 @20°C (Ω/km) | Class 5 软铜电阻 @20°C (Ω/km) | 约等 AWG | 常见用途 |
|---------------|--------------|------------------------------|------------------------------|---------|---------|
| 0.5 | 0.798 | 36.0 | 39.0 | 20 | 信号线、弱电控制线、屏蔽引线 |
| 0.75 | 0.977 | 24.5 | 26.0 | 18 | 控制线、灯线、二次回路 |
| 1.0 | 1.128 | 18.1 | 19.5 | 17 | 控制回路、仪器仪表引线 |
| 1.5 | 1.382 | 12.1 | 13.3 | 15 | 环路线圈本体、照明支路 |
| 2.5 | 1.784 | 7.41 | 7.98 | 13 | 环路线圈本体、插座回路、道闸电源 |
| 4 | 2.257 | 4.61 | 4.95 | 11 | 道闸/电机主回路、空调回路 |
| 6 | 2.764 | 3.08 | 3.3 | 9 | 道闸电机、小功率设备进线 |
| 10 | 3.568 | 1.83 | 1.91 | 7 | 设备电源进线、充电桩支路 |
| 16 | 4.514 | 1.15 | 1.21 | 5 | 配电支路、充电桩回路 |
| 25 | 5.642 | 0.727 | 0.78 | 3 | 配电干路、进线 |
| 35 | 6.676 | 0.524 | 0.554 | 2 | 总进线、充电桩干线 |
| 50 | 7.979 | 0.387 | 0.386 | 1/0 | 总进线、母排连接 |
| 70 | 9.441 | 0.268 | 0.272 | 2/0 | 大功率进线 |
| 95 | 10.998 | 0.193 | 0.206 | 3/0 | 低压出线、大功率回路 |
| 120 | 12.361 | 0.153 | 0.161 | 4/0 | 低压主进线 |
| 150 | 13.820 | 0.124 | 0.129 | — | 低压主进线 |
| 185 | 15.348 | 0.0991 | 0.106 | — | 低压主进线 |
| 240 | 17.481 | 0.0754 | 0.0801 | — | 低压主进线、密集型母线 |
| 300 | 19.544 | 0.0601 | 0.0641 | — | 低压主进线、母线槽 |
| 400 | 22.568 | 0.047 | 0.0486 | — | 大截面电缆、母线 |
| 500 | 25.231 | 0.0366 | 0.0384 | — | 大截面电缆、母线 |
| 630 | 28.322 | 0.0287 | 0.0287 | — | 大截面电缆、母线 |
| 标称截面 (mm²) | 等效直径 (mm) | Class 1/2 电阻 @20°C (Ω/km) | Class 5 软铜电阻 @20°C (Ω/km) | 约等 AWG | PVC 载流量参考 (A) | XLPE 载流量参考 (A) | 常见用途 |
|---------------|--------------|----------------------------|------------------------------|---------|-------------------|--------------------|---------|
| 0.5 | 0.798 | 36.0 | 39.0 | 20 | 10 | — | 信号线、弱电控制线、屏蔽引线 |
| 0.75 | 0.977 | 24.5 | 26.0 | 18 | 13 | — | 控制线、灯线、二次回路 |
| 1.0 | 1.128 | 18.1 | 19.5 | 17 | 16 | — | 控制回路、仪器仪表引线 |
| 1.5 | 1.382 | 12.1 | 13.3 | 15 | 20 | 24 | 环路线圈本体、照明支路 |
| 2.5 | 1.784 | 7.41 | 7.98 | 13 | 27 | 32 | 环路线圈本体、插座回路、道闸电源 |
| 4 | 2.257 | 4.61 | 4.95 | 11 | 36 | 42 | 道闸/电机主回路、空调回路 |
| 6 | 2.764 | 3.08 | 3.3 | 9 | 46 | 54 | 道闸电机、小功率设备进线 |
| 10 | 3.568 | 1.83 | 1.91 | 7 | 63 | 57 | 设备电源进线、充电桩支路 |
| 16 | 4.514 | 1.15 | 1.21 | 5 | 85 | 76 | 配电支路、充电桩回路 |
| 25 | 5.642 | 0.727 | 0.78 | 3 | 112 | 101 | 配电干路、进线 |
| 35 | 6.676 | 0.524 | 0.554 | 2 | 138 | 124 | 总进线、充电桩干线 |
| 50 | 7.979 | 0.387 | 0.386 | 1/0 | 168 | 149 | 总进线、母排连接 |
| 70 | 9.441 | 0.268 | 0.272 | 2/0 | 213 | 188 | 大功率进线 |
| 95 | 10.998 | 0.193 | 0.206 | 3/0 | 258 | 226 | 低压出线、大功率回路 |
| 120 | 12.361 | 0.153 | 0.161 | 4/0 | 299 | 261 | 低压主进线 |
| 150 | 13.820 | 0.124 | 0.129 | — | 344 | 299 | 低压主进线 |
| 185 | 15.348 | 0.0991 | 0.106 | — | 392 | 340 | 低压主进线 |
| 240 | 17.481 | 0.0754 | 0.0801 | — | 461 | 400 | 低压主进线、密集型母线 |
| 300 | 19.544 | 0.0601 | 0.0641 | — | 530 | 458 | 低压主进线、母线槽 |
| 400 | 22.568 | 0.047 | 0.0486 | — | 620 | 540 | 大截面电缆、母线 |
| 500 | 25.231 | 0.0366 | 0.0384 | — | 705 | 620 | 大截面电缆、母线 |
| 630 | 28.322 | 0.0287 | 0.0287 | — | 800 | 720 | 大截面电缆、母线 |
## 二、导体分类(GB/T 3956 / IEC 60228
| 类别 | 结构 | 典型应用 |
@@ -49,14 +52,20 @@
- 表中 AWG 列为"截面最接近"对照,仅供进口线材/元件换算参考;国内工程选型一律以 mm² + GB/T 3956 电阻为准。
- 速记:mm² → AWG,截面除以 2 约为 AWG 号 +3(如 10→5 mm²,AWG 7→10)。
## 四、环路线圈应用备注(车检器
## 四、载流量降额要点(现场选线必看
1. **敷设方式**:空气中明敷 > 桥架 > 穿管 > 直埋。穿管多根并敷,载流量下降明显(2~4 根管约 ×0.8~0.6)。
2. **环境温度**PVC 基准 30°C、XLPE 基准 40°C;温度升高需乘温度校正系数(如 40°C 时 PVC 约 ×0.87)。
3. **电压降校核**:长距离回路除载流量外必须校压降(ΔU = I×L×R),一般 ≤5%。环路引线虽电流小,但几十 kHz 下分布参数影响大于直流电阻,线规按机械强度选即可。
## 五、环路线圈应用备注(车检器)
1. **线圈本体绕线**:常用 1.5~2.5 mm² 多股软铜线(Class 5,BVR 类),绝缘耐温 ≥105°C、绝缘耐压 ≥500V——切缝积水、电缆沟潮湿环境必须扛得住。
2. **引线到检测器**:推荐屏蔽双绞线 0.3~0.5 mm²(对应 AWG 22~24),绞距要密,屏蔽层单端接地。别用太细的线(<0.5 mm²),端子压接处容易断。
3. **注意**:环路工作在几十 kHz 振荡,趋肤效应影响小,多股线即可。但引线超过 50m 时要考虑分布电容对振荡频率的影响——**线规不是唯一变量**,引线长度和绞合方式同样关键。
4. 检测器端子电流是 mA 级,线规主要看机械强度与压接可靠性,不必按载流量选。
## 、关联文档
## 、关联文档
- AWG 为主表的完整对照(AWG 4/0 ~ 30,含载流量):见同目录 `awg对照表.md` / `awg对照表.csv`
- 本表数据文件:`线规对照表_mm2_GB3956.csv`